R410A-15bl

R410A, a mixed refrigerant composing of difluoromethane and pentafluoroethane.

Molecular formula: CH₂F₂/CHF₂CF₃

R410A Chemical Product Safety Technical Instruction
R410A Refrigerant Pressure-enthalpy Diagram
R410A Refrigerant Temperature-pressure Parallel Table

Weihua Refrigeration R410A Product Quality Implementation Standard (AHRI-700-2016):

Item AHRI-700-2016Excellent product Weihua Refrigerants,  R410A Product Quality Index
Character Colorless, Clear , Odorless Colorless, Clear , Odorless
Mass fraction of R32/% 48.5~50.5 48.5~50.5
Mass fraction of R125/% 49.5~51.5 49.5~51.5
Mass fraction of R410A/% 99.5 99.9
Mass fraction of water/% 0.001 0.001
Mass fraction of acid(Based on HCL)/% 0.00001 0.00001
Mass fraction of evaporation residue/% 0.01 0.01
Chloride (CL) test Pass Pass
Volume fraction of non-condensable gas(25℃)/% 1.5 1.5

Packing specification:


Disposable steel cylinder package: 5kg(11lbs), 10kg(22lbs), 11.3kg(25lbs), customizable
Refillable steel cylinder: 60L, 400L, 926L and ISO tanks

Application Area:


As a medium and high temperature refrigerant widely used today, R410A is mainly used in household air conditioners, small and medium commercial air conditioners (small and medium unit air conditioners, household central air conditioners, multi-unit conditioners), mobile air conditioners (automobile air conditioners, etc.), dehumidifiers, refrigerating dryers, vessel refrigeration equipment, and industrial refrigeration equipment, etc.

Storage and transportation (safety classification A1) :


The steel cylinder used to store R410A refrigerant is a type of pressure vessel, so keep it away from fire, heat sources, and direct sunlight, store it in a cool, dry and ventilated warehouse. Handle lightly to prevent crushing, collision, and prevent breakage to the cylinder or accessories such as valve, etc.

Lubricant recommendations :


Compatible with ester lubricants (POE)

Tips: Selection of refrigerating oil for different types of equipment and different scenarios shall follow the recommendations of the refrigeration compressor and refrigeration (conditioning) equipment manufacturers, or be determined based on the equivalent design and technician requirement according to the specific conditions of the refrigeration compressor and refrigeration equipment, that is, using only the refrigerating oil that matches the equipment or its application purpose.